Training / AVCleared Installation Specialist / Lesson 3 of 7
Pathways and cable management
Supports, conduit fill, pulling, separation from power and keeping cable in spec.
About 12 minutes
Support
Low-voltage cable above ceilings must be supported by its own means, such as J-hooks, cable tray or dedicated support wires attached to the structure. A common rule of thumb from the structured cabling standards is support at intervals of no more than about 5 ft (1.5 m). Never lay cable on ceiling tiles or fasten it to sprinkler pipes, ducts or other trades' supports.
Conduit
- Follow conduit fill limits. Under the US electrical code, conduit holding more than two cables is generally limited to 40% of its cross-section.
- Respect bend radius and pulling tension, and use lubricant for long pulls.
- Leave a pull string in place for future cables.
- Bush or protect conduit ends so cable jackets aren't cut.
Separation
Keep low-voltage and video cables away from power and from noisy sources like motors and lighting ballasts. Where they must cross, cross at a right angle. Keep speaker-level cables apart from microphone and line-level cables in shared pathways.
Dressing cable
- Use hook-and-loop straps rather than overtightened cable ties; crushing twisted-pair cable deforms it and hurts performance.
- Keep bundles neat and sized so heat can escape, especially with PoE.
- Leave service loops where equipment may need to be pulled out later.
Neat cable isn't vanity. It is faster to service, more reliable, and it's the first thing an inspector or client looks at.